Huawei Test Burns Transformer Station for 80 Hours
Huawei Digital Power's fire test in a LUTERRA battery sub-array kept the blaze confined to a transformer station, with no spread to nearby battery containers.
Updated on Nov. 23, 2026 in Energy

On Oct. 30, 2026, Huawei Digital Power ignited an oil-filled transformer station inside a LUTERRA battery sub-array, and the fire burned for 80 hours without manual intervention. Huawei said the blaze did not spread to the battery containers, which stood 0.6 m apart.
Why it matters
The test addresses how fire could move between closely spaced battery enclosures and nearby oil-filled equipment at utility-scale energy storage sites. Its results may inform safety design choices as grid-scale storage expands.
The test used a 5-ton oil-filled transformer station and through-busbars linking the containers, with INERIS helping set abuse conditions to match the AMPG 2925-2 standard. The release does not report how the results would translate to sites with different spacing or equipment layouts.
The players
Huawei Digital Power
Huawei Digital Power is the energy division of Chinese technology company Huawei, which develops power conversion and energy storage products.
SGS
SGS is a Swiss-headquartered testing, inspection and certification company that organised and ran the fire test.
INERIS
INERIS is France's National Institute for Industrial Environment and Risks, which helped set the abuse conditions for the test.
The details
SGS organised and ran the test, which was witnessed by INERIS, Bureau Veritas, BCFI and the Tianjin Fire Research Institute. The transformer station was ignited from outside under full-oil condition, and Huawei said the results were validated against the AMPG 2925-2 framework.
Timeline
Oct. 30, 2026: Transformer station ignited and the 80-hour burn test began.
Nov. 20, 2026: Huawei issued a release describing the test.
Roadmap
The US NFPA 855 standard sets a 3 ft (914 mm) minimum separation between battery energy storage units, and this test used a 0.6 m gap to examine fire spread. The result adds a data point to an ongoing debate over how tightly grid-scale storage can be packed.
Future storage projects may face different spacing and fire-protection requirements depending on how regulators and insurers weigh tests like this one. Operators planning large battery sites will need to track which standards apply in their jurisdiction.
The takeaway
Storage site layout and spacing remain central to limiting fire spread between battery and oil-filled equipment. Readers following grid-scale energy should watch how safety rules respond to tests like this.